Air Comfort receives Gilbane Building Company Award of Excellence for SBC Harvey project
Air Comfort University officially opens
Air Comfort certified as an MSCA Star contractor
Controls Corner
How Did We Do?




Did You Know?
The condenser coil on your air conditioner uses unfiltered outdoor air to reject heat and therefore requires cleaning. A dirty coil that only raises the condensing temperature 10 degrees, reduces capacity 7% and adds 10% in power consumption.

How I Learned to Close the Door
by Fred Litke

Remember when your dad told you to “Close that door! We’re not cooling the great outdoors!” How we’ve grown. We wouldn’t think twice about wasting energy like that anymore, would we? I mean it’s simply not done. Who would be so wasteful?

Would it break your heart to find out that we probably are?

Commercial heating\cooling ventilating systems have the ability to introduce fresh outdoor air into the served spaces. The quantity of this outdoor air is based in the maximum expected or design occupancy. Dampers are set to a prescribed and measured minimum position to allow for this.

The minimum outdoor air intake rate is 15 to 20 cubic feet per minute (cfm), per person. So if the design occupancy is 100 people, you would set the system to deliver at least 1,500 cfm or 90,000 cubic feet of outdoor air per hour. That is the “Solution to Pollution is Dilution” approach. That’s enough to completely replace all the air in a 1,125 square foot home 10 times per hour…dad would have blown a gasket!

Providing all 100 of those people fresh air is a good thing. Problem is, 100 people are there at maximum occupancy. The remaining time there is less, maybe a lot less. Still those dampers are set to provide the same amount of outdoor air.

You see where I’m going with this thing? Yeah, that’s right, let’s close that damper. But how? And how much? If I close it too much it would not provide adequate indoor air quality and if I leave it open I’m conditioning the “Great Outdoors”.

It surely wouldn’t make sense to count heads in and out and make constant manual adjustments. That would be too labor intensive. So does that mean you’re stuck with the maximum minimum all the time? No. As a matter of fact there is a good way to test for proper ventilation.

A newer control strategy called Demand Control Ventilation (DCV) uses a space CO2 (Carbon Dioxide) level monitor to adjust the outdoor air intake. CO2 is a very good indicator of occupancy level. Technology has made CO2 sensors accurate, stable and affordable. Now outdoor air intake can be automatically readjusted based on the level of CO2 in the space. This will insure that we use the minimum outdoor air intake at minimum occupancy while providing for maximum intake at maximum occupancy.

Now that would have made dad happy.



<< back to controls corner